4.40 DHWLOOPSEG
DHWLOOPSEG constructs one or more objects representing a segment of the preceeding DHWLOOP. A DHWLOOP can have any number of DHWLOOPSEGs to represent the segments of the loop with possibly differing sizes, insulation, or surrounding conditions.
wgName
Optional name of segment; give after the word “DHWLOOPSEG” if desired.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
63 characters | none | No | constant |
wgTy=choice
Specifies the type of segment. RETURN segments, if any, must follow SUPPLY segments.
SUPPLY | Indicates a supply segment (flow is sum of circulation and draw flow, child DHWLOOPBRANCHs permitted). |
RETURN | Indicates a return segment (flow is only due to circulation, child DHWLOOPBRANCHs not allowed) |
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
none | Yes | constant |
wgLength=float
Length of segment.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
ft | x \(\ge\) 0 | 0 | No | constant |
wgSize=float
Nominal size of pipe. CSE assumes the pipe outside diameter = size + 0.125 in.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
in | x \(>\) 0 | 1 | Yes | constant |
wgInsulK=float
Pipe insulation conductivity
Units | Legal Range | Default | Required | **Variability |
---|---|---|---|---|
Btuh-ft/ft2-oF | x \(>\) 0 | 0.02167 | No | constant |
wgInsulThk=float
Pipe insulation thickness
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
in | x \(\ge\) 0 | 1 | No | constant |
wgExH=float
Combined radiant/convective exterior surface conductance between insulation (or pipe if no insulation) and surround.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
Btuh/ft2-oF | x \(>\) 0 | 1.5 | No | hourly |
wgExT=float
Surrounding equivalent temperature.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
oF | x \(>\) 0 | 70 | No | hourly |
wgFNoDraw=float
Fraction of hour when no draw occurs.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
oF | x \(>\) 0 | 70 | No | hourly |
endDHWLoopSeg
Optionally indicates the end of the DHWLOOPSEG definition.
Units | Legal Range | Default | Required | Variability |
---|---|---|---|---|
none | No |
Related Probes: