6.6 chiller (owner: coolPlant)
@chiller[1..].
Name | Input? | Runtime? | Type | Variability | Description |
---|---|---|---|---|---|
name | X | X | string | constant | – |
chCapDs | X | X | number | autosize and simulate phase start time | Capacity at chdsts,chdstcnd, btuh. required. negative internally. niles capdsn. |
chTsDs | X | X | number | autosize and simulate phase start time | Temp leaving chiller at which chcapds applies, default 44. niles twsudsn. |
chTcndDs | X | X | number | autosize and simulate phase start time | Temp entering condenser (twodel value) for chcapds, default 85. niles twcnddsn. |
chPyCapT.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyCapT.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyCapT.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyCapT.k[3] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyCapT.k[4] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyCapT.k[5] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyCapT.k[6] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chCop | X | X | number | autosize and simulate phase start time | Full-load coefficient of performance (output btu/input btu) @ chtsds/chtcndds, reflecting |
chEirDs | X | X | number | run start time (of each phase, autoSize or simulate) | Full-load eir (energy input ratio) @ chtsds/chtcndds, relecting motor and chiller efficiency. |
chPyEirT.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirT.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirT.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirT.k[3] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirT.k[4] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirT.k[5] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirT.k[6] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirUl.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirUl.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirUl.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirUl.k[3] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chPyEirUl.k[4] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chMinUnldPlr | X | X | number | autosize and simulate phase start time | Min unloading loading part load ratio, default 0.1. niles minunldplr. |
chMinFsldPlr | X | X | number | autosize and simulate phase start time | Min false loading part load ratio, default 0.1. niles minfsldplr. must be <= chminunldplr. |
chMotEff | X | X | number | autosize and simulate phase start time | Motor efficiency (poorly named), default 1.0, niles motoreff, used only to determine |
mtri | X | X | integer number | input time | Meter name (“chmtr”) for accumulating compressor energy used by chiller, |
chpp.gpm | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chpp.hdLoss | X | X | number | autosize and simulate phase start time | – |
chpp.motEff | X | X | number | autosize and simulate phase start time | – |
chpp.hydEff | X | X | number | autosize and simulate phase start time | – |
chpp.ovrunF | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chpp.mtri | X | X | integer number | autosize and simulate phase start time | Meter name (“chmtr”) for accumulating compressor energy used by chiller, |
chpp.mw | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chpp.q | X | X | number | run start time (of each phase, autoSize or simulate) | This chiller’s current primary output power to pri loop |
chpp.p | X | X | number | run start time (of each phase, autoSize or simulate) | Compressor power input. also see chpp.p, chcp.p. (niles cndpmppwrin, prmpmppwrin, totpwrin) |
chcp.gpm | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chcp.hdLoss | X | X | number | autosize and simulate phase start time | – |
chcp.motEff | X | X | number | autosize and simulate phase start time | – |
chcp.hydEff | X | X | number | autosize and simulate phase start time | – |
chcp.ovrunF | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chcp.mtri | X | X | integer number | autosize and simulate phase start time | Meter name (“chmtr”) for accumulating compressor energy used by chiller, |
chcp.mw | X | X | number | run start time (of each phase, autoSize or simulate) | – |
chcp.q | X | X | number | run start time (of each phase, autoSize or simulate) | This chiller’s current primary output power to pri loop |
chcp.p | X | X | number | run start time (of each phase, autoSize or simulate) | Compressor power input. also see chpp.p, chcp.p. (niles cndpmppwrin, prmpmppwrin, totpwrin) |
auxOn | X | X | number | hourly | Addl input energy used in proportion to plr when on, default 0, hourly vbl for future flexblty. |
auxOnMtri | X | X | integer number | input time | Mtr to which to charge “auxon” |
auxOff | X | X | number | hourly | Addl input energy when off for part or all of subhr (proportional to 1-plr), for unforseen uses. |
auxOffMtri | X | X | integer number | input time | Mtr for “auxoff” |
auxOnAtall | X | X | number | hourly | Addl input energy used in toto when chiller on for any part of subhour, for unforseen uses. |
auxOnAtallMtri | X | X | integer number | input time | Mtr for “auxonatall” |
auxFullOff | X | X | number | hourly | Additional input energy when off for entire subhour (as opposed to in proportion to 1-plr). |
auxFullOffMtri | X | X | integer number | input time | Mtr to which auxfulloff is charged, default c.mtri. |
nxCh4cp | X | X | integer number | run start time (of each phase, autoSize or simulate) | 0 or subscript of next chiller in same coolplant. 1st is coolplant.ch1. |
used | X | X | integer number | run start time (of each phase, autoSize or simulate) | Non-0 if a coolplant uses this chiller – else warning |
eirMinUnldPlr | X | X | number | run start time (of each phase, autoSize or simulate) | Chpyeirul(minunldplr): precomputed energy input corr for false loading, prorate for cycling |
chMode | X | X | unrecognized | end of each subhour | C_offonch_off or _on: whether this chiller is running, set by staging code. |
cap | X | X | number | end of each subhour | – |
q | X | X | number | end of each subhour | This chiller’s current primary output power to pri loop |
p | X | X | number | end of each subhour | Compressor power input. also see chpp.p, chcp.p. (niles cndpmppwrin, prmpmppwrin, totpwrin) |
pAuxOn | X | X | number | end of each subhour | Chiller-on proporotinal aux power this subhour |
pAuxOff | X | X | number | end of each subhour | Chiller-off proportional aux power this subhour |
pAuxOnAtall | X | X | number | end of each subhour | Chiller on-at-all aux power this subhour |
pAuxFullOff | X | X | number | end of each subhour | Auxfulloff power this subhour |