ashpTy |
choice:WHASHPTY |
input time |
- air source heat pump (HPWH) type, required iff wh_heatSrc=ASHPX, else ignored
- C_WHASHPTYCH_xxx, etc
|
resTy |
choice:WHRESTY |
input time |
- resistance heater type, used iff wh_heatSrc=_ELRESX, else ignored
- C_WHRESTYCH_xxx, etc
- documentation only (9-2021)
|
znTi |
TI |
input time |
- [DHWHEATER][dhwheater] location zone re tank loss
- 0 iff wh_tEx being used
- heat losses go to half to zone air / half radiant
|
tEx |
number |
Start of subhour |
- surrounding temperature, F for tank loss
- when wh_tEx set
- - wh_znTi ignored
- - heat loss discarded
|
ashpSrcZnTi |
TI |
input time |
- ASHP source zone
- 0 iff wh_ashpTSrc being used
- input heat removed from zone air
|
ashpTSrc |
number |
Start of subhour |
- ASHP source temperature, F
- when wh_ashpTSrc set
- - wh_ashpSrcZnTi ignored
- - heat transfer ignored
|
ashpResUse |
FLOAT_GZ |
input time |
- resistance heat parameter for
- Ecotope HPWH model iff C_WHASHPTYCH_GENERIC
- default = 7.22, units / meaning unknown
|
tankTInit[index] |
FLOAT_GZ Array [DIM_DHWTANKTINIT] |
Start of run |
- initial tank layer temperatures for HPWH types, F (12 values)
- [0]=bottom layer / [11]=top layer
- HPWH tank model layer temps initialized at beginning of warmup
- (not reinitialized at beg of simulation)
- [0]=bottom layer / [11]=top layer
|
tankCount |
FLOAT_GZ |
Start of run |
- # of storage tanks per [DHWHEATER][dhwheater], re built-up whType=Builtup (default=1)
- note does *not* reflect wh_mult (wh_mult=2, wh_tankCount=3 -> 6 tanks)
|
heatingCap |
FLOAT_GZ |
Start of run |
- Nominal heating capacity, Btuh
- available only for limited HPWH types
|
vol |
FLOAT_GEZ |
Start of run |
- total storage vol, gal (actual, not rated; not per tank)
- HPWH types: sets vol (default from preset)
- other types: documentation only (default 50)
|
volRunning |
FLOAT_GZ |
input time |
- running storage volume = vol above aquastat, gal
- HPWH compressor types: determines reqd total volume based on
- aquastat position; see HPWHLINK::hw_DeriveVolFromVolRunning()
|
UA |
FLOAT_GEZ |
Start of run |
- HPWH-type total UA, Btuh/F (not per tank)
- default from HPWH preset
|
insulR |
FLOAT_GZ |
Start of run |
- HPWH-type tank insulation resistance, hr-F/Btuh
- default from preset or wh_UA and wh_vol
|
inHtSupply |
number |
input time |
- fractional tank height of supply inlet (0=bottom, 1=top)
- default 0, HPWH models only
|
inHtLoopRet |
number |
input time |
- fractional tank height of loop return inlet(s) (0=bottom, 1=top)
- default 0, HPWH models only
|
EF |
FLOAT_GZ |
input time |
rated energy factor |
LDEF |
FLOAT_GZ |
input time |
load-dependent energy factor |
UEF |
FLOAT_GZ |
input time |
- rated uniform energy factor
- re C_WHTYPECH_INSTUEF
|
ratedFlow |
FLOAT_GZ |
input time |
max rated flow per UEF test, gpm |
annualFuel |
FLOAT_GEZ |
input time |
annual fuel use per UEF method, therms/yr |
annualElec |
FLOAT_GEZ |
input time |
annual electricity use per UEF method, kWh/yr |