ZONE

ZONE constructs an object of class ZONE, which describes an area of the building to be modeled as having a uniform condition. ZONEs are large, complex objects and can have many subobjects that describe associated surfaces, shading devices, HVAC equipment, etc.

ZONE General Members

znName

Name of zone. Enter after the word ZONE; no "=" is used.

Units Legal Range Default Required Variability
63 characters none Yes constant

znModel

Type: choice

Selects model for zone.

CNE Older central difference model based on original CALPAS methods. Not fully supported and not suitable for current compliance applications.
CZM Conditioned zone model. Forward-difference, short time step methods are used.
UZM Unconditioned zone model. Identical to CZM except heating and cooling are not supported. Typically used for attics, garages, and other ancillary spaces.
Units Legal Range Default Required Variability
choices above CNE No constant

znArea

Type: float

Nominal zone floor area.

Units Legal Range Default Required Variability
ft2 x \(>\) 0 none Yes constant

znVol

Type: float

Nominal zone volume.

Units Legal Range Default Required Variability
ft3 x \(>\) 0 none Yes constant

znAzm

Type: float

Zone azimuth with respect to bldgAzm. All surface azimuths are relative to znAzm, so that the zone can be rotated by changing this member only. Values outside the range 0o to 360o are normalized to that range.

Units Legal Range Default Required Variability
degrees unrestricted 0 No constant

znFloorZ

Type: float

Nominal zone floor height relative to arbitrary 0 level. Used re determination of vent heights

Units Legal Range Default Required Variability
ft unrestricted 0 No constant

znCeilingHt

Type: float

Nominal zone ceiling height relative to zone floor (typically 8 – 10 ft).

Units Legal Range Default Required Variability
ft x \(>\) 0 znVol / znArea No constant

znEaveZ

Type: float

Nominal eave height above ground level. Used re calculation of local surface wind speed. This in turn influences outside convection coefficients in some surface models and wind-driven air leakage.

Units Legal Range Default Required Variability
ft x \(>\) 0 znFloorZ + infStories*8 No constant

znCAir

Type: float

Zone "air" heat capacity: represents heat capacity of air, furniture, "light" walls, and everything in zone except surfaces having heat capacity (that is, non-QUICK surfaces).

Units Legal Range Default Required Variability
Btu/oF x \(\geq\) 0 3.5 * znArea No constant

znHcAirX

Type: float

Zone air exchange rate used in determination of interior surface convective coefficients. This item is generally used only for model testing.

Units Legal Range Default Required Variability
ACH x \(>\) 0 as modeled No subhourly

znHcFrcF

Type: float

Zone surface forced convection factor. Interior surface convective transfer is modeled as a combination of forced and natural convection. hcFrc = znHcFrcF * znHcAirX^.8. See CSE Engineering Documentation.

Units Legal Range Default Required Variability
Btuh/ft2-oF .2 .2 No hourly

znHIRatio

Type: float

Zone hygric inertia ratio. In zone moisture balance calculations, the effective dry-air mass = znHIRatio * (zone dry air mass). This enhancement can be used to represente the moisture storage capacity of zone surfaces and contents.

Units Legal Range Default Required Variability
x \(>\) 0 1 No constant

znSC

Type: float

Zone shade closure. Determines insolation through windows (see WINDOW members wnSCSO and wnSCSC) and solar gain distribution: see SGDIST members sgFSO and sgFSC. 0 represents shades open; 1 represents shades closed; intermediate values are allowed. An hourly variable CSE expression may be used to schedule shade closure as a function of weather, time of year, previous interval HVAC use or zone temperature, etc.

Units Legal Range Default Required Variability
0 \(\leq\) x \(\leq\) 1 1 when cooling was used in previous hour, else 0 No hourly

znTH

Type: float

Heating set point used (and required) when znModel=CZM and zone has no terminals.

Units Legal Range Default Required Variability
oF 0 < znTH < znTC none Per above subhourly

znTD

Type: float

Desired set point (temperature maintained with ventilation if possible) for znModel=CZM. Must be specified when zone ventilation is active.

Units Legal Range Default Required Variability
oF x > 0; znTH < znTD < znTC none if venting subhourly

znTC

Type: float

Cooling set point used (and required) when znModel=CZM and zone has no terminals.

Units Legal Range Default Required Variability
oF 0 < znTC > znTH none Per above subhourly

znModel = CZM zone heating and cooling is provided either via an RSYS HVAC system, by "magic" heat transfers specified by znQxxx items, or via TERMINAL (s). One of these must be defined.

znRSys

Type: rsysName

Name of RSYS providing heating, cooling, and optional central fan integrated ventilation to this zone.

Units Legal Range Default Required Variability
RSYS name (no RSYS) No constant

znQMxH

Type: float

Heating capacity at current conditions

Units Legal Range Default Required Variability
Btuh x \(\geq\) 0 none No hourly

znQMxHRated

Type: float

Rated heating capacity

Units Legal Range Default Required Variability
Btuh x \(\geq\) 0 none No constant

znQMxC

Type: float

Cooling capacity at current conditions

Units Legal Range Default Required Variability
Btuh x \(\leq\) 0 none No hourly

znQMxCRated

Type: float

Rated cooling capacity

Units Legal Range Default Required Variability
Btuh x \(\leq\) 0 none No constant

<% if comfort_model %> The following provide parameters for comfort calculations

znComfClo

Type: float

Occupant clothing resistance, used only when a comfort model is enabled.

Units Legal Range Default Required Variability
clo x \(\geq\) 0 none No subhourly

znComfMet

Type: float

Occupant metabolic rate, used only when a comfort model is enabled.

Units Legal Range Default Required Variability
met x \(\geq\) 0 none No hourly

znComfAirV

Type: float

Nominal air velocity used for comfort model, used only when a comfort model is enabled.

Units Legal Range Default Required Variability
x \(\geq\) 0 none No Hourly

znComfRh

Type: float

Nominal zone relative humidity used for comfort model, used only when a comfort model is enabled.

Units Legal Range Default Required Variability
0 \(\leq\) x \(\leq\) 1 none No hourly

<% end %>

ZONE Infiltration

The following control a simplified air change plus leakage area model. The Sherman-Grimsrud model is used to derive air flow rate from leakage area and this rate is added to the air changes specified with infAC. Note that TOP.windF does not modify calculated infiltration rates, since the Sherman-Grimsrud model uses its own modifiers. See also AirNet models available via IZXFER.

infAC

Type: float

Zone infiltration air changes per hour.

Units Legal Range Default Required Variability
1/hr x \(\geq\) 0 0.5 No hourly

infELA

Type: float

Zone effective leakage area (ELA).

Units Legal Range Default Required Variability
in2 x \(\geq\) 0 0.0 No hourly

infShld

Type: int

Zone local shielding class, used in derivation of local wind speed for ELA infiltration model, wind-driven AirNet leakage, and exterior surface coefficients. infShld values are --

1 no obstructions or local shielding
2 light local shielding with few obstructions
3 moderate local shielding, some obstructions within two house heights
4 heavy shielding, obstructions around most of the perimeter
5 very heavy shielding, large obstructions surrounding the perimeter within two house heights
Units Legal Range Default Required Variability
1 \(\leq\) x \(\leq\) 5 3 No constant

infStories

Type: int

Number of stories in zone, used in ELA model.

Units Legal Range Default Required Variability
1 \(\leq\) x \(\leq\) 3 1 No constant

znWindFLkg

Type: float

Wind speed modifier factor. The weather file wind speed is multiplied by this factor to yield a local wind speed for use in infiltration and convection models.

Units Legal Range Default Required Variability
x \(\geq\) 0 derived from znEaveZ and infShld No constant

znAFMtr

Type: afMtrName

Name of an AFMETER object, if any, to which zone AirNet air flows are recorded. ZnAFMtr defines a pressure boundary for accounting purposes. Multiple zones having the same AFMETER are treated as a single volume -- interzone flows within that volume are not recorded. For example, to obtain "building total" flow data, a common AFMETER could be assigned to several conditioned zones but not to adjacent unconditioned zones such as attic spaces.

Units Legal Range Default Required Variability
name of an AFMETER not recorded No constant

znLoadMtr

Type: ldMtrName

Name of a LOADMETER object, if any, to which zone heating and cooling loads are recorded.

Units Legal Range Default Required Variability
name of a LOADMETER not recorded No constant

ZONE Exhaust Fan

Presence of an exhaust fan in a zone is indicated by specifying a non-zero design flow value (xfanVfDs).

Zone exhaust fan model implementation is incomplete as of July, 2011. The current code calculates energy use but does not account for the effects of air transfer on room heat balance. IZXFER provides a more complete implementation.

xfanFOn

Type: float

Exhaust fan on fraction. On/off control assumed, so electricity requirement is proportional to run time.

Units Legal Range Default Required Variability
fraction 0 \(\leq\) x \(\leq\) 1 1 No hourly

Example: The following would run an exhaust fan 70% of the time between 8 AM and 5 PM:

    xfanFOn = select( (\$hour >= 7 && \$hour < 5), .7,
                                          default, 0 );

xfanVfDs

Type: float

Exhaust fan design flow; 0 or not given indicates no fan.

Units Legal Range Default Required Variability
cfm x \(\geq\) 0 0, no fan If fan present constant

xfanPress

Type: float

Exhaust fan external static pressure.

Units Legal Range Default Required Variability
inches 0.05 \(\leq\) x \(\leq\) 1.0 0.3 No constant

Only one of xfanElecPwr, xfanEff, and xfanShaftBhp may be given: together with xfanVfDs and xfanPress, any one is sufficient for CSE to detemine the others and to compute the fan heat contribution to the air stream.

xfanElecPwr

Type: float

Fan input power per unit air flow (at design flow and pressure).

Units Legal Range Default Required Variability
W/cfm x \(>\) 0 derived from xfanEff If xfanEff and xfanShaftBhp not present constant

xfanEff

Type: float

Exhaust fan/motor/drive combined efficiency.

Units Legal Range Default Required Variability
fraction 0 \(\leq\) x \(\leq\) 1 0.08 No constant

xfanShaftBhp

Type: float

Fan shaft power at design flow and pressure.

Units Legal Range Default Required Variability
BHP x \(>\) 0 derived from xfanElecPwr and xfanVfDs If xfanElecPwr not present constant

xfanMtr

Type: mtrName

Name of METER object, if any, by which fan's energy use is recorded (under end use category "fan").

Units Legal Range Default Required Variability
name of a METER not recorded No constant

endZone

Indicates the end of the zone definition. Alternatively, the end of the zone definition can be indicated by the declaration of another object or by "END". If END or endZone is used, it should follow the definitions of the ZONE's subobjects such as GAINs, SURFACEs, TERMINALs, etc.

Units Legal Range Default Required Variability
none No constant