RSYS

RSYS constructs an object representing an air-based residential HVAC system.

rsName

Optional name of HVAC system; give after the word “RSYS” if desired.

Units Legal Range Default Required Variability
63 characters none No constant

rsType

Type: choice

Type of system.

rsType Description
ACFURNACE Compressor-based cooling modeled per SEER and EER. Fuel-fired heating. Primary heating input energy is accumulated to end use HTG of meter rsFuelMtr.
ACPMFURNACE Compressor-based cooling modeled per PERFORMANCEMAP specified in rsPerfMapClg. Fuel-fired heating. Primary heating input energy is accumulated to end use HTG of meter rsFuelMtr.
ACRESISTANCE Compressor-based cooling and electric ('strip') heating. Cooling performance based on SEER and EER. Primary heating input energy is accumulated to end use HTG of meter rsElecMtr.
ACPMRESISTANCE Cooling based on PERFORMANCEMAP specified in rsPerfMapClg. Primary heating input energy is accumulated to end use HTG of meter rsElecMtr.
ASHP Air-source heat pump (compressor-based heating and cooling). Primary (compressor) heating input energy is accumulated to end use HTG of meter rsElecMtr. Auxiliary and defrost heating input energy is accumulated to end use HPBU of meter rsElecMtr or meter rsFuelMtr (depending on rsTypeAuxH).
ASHPKGROOM Packaged room air-source heat pump.
ASHPHYDRONIC Air-to-water heat pump with hydronic distribution. Compressor performance is approximated using the air-to-air model with adjusted efficiencies.
ASHPPM Air-to-air heat pump modeled per PERFORMANCMAPs specified via rsPerfMapHtg and rsPerfMapClg.
WSHP Water-to-air heat pump.
AC Compressor-based cooling; no heating. Required ratings are SEER and capacity and EER at 95 oF outdoor dry bulb.
ACPM Compressor-based cooling modeled per PERFORMANCEMAP specified in rsPerfMapClg; no heating.
ACPKGROOM Packaged compressor-based cooling; no heating. Required ratings are capacity and EER at 95 oF outdoor dry bulb.
FURNACE Fuel-fired heating. Primary heating input energy is accumulated to end use HTG of meter rsFuelMtr.
RESISTANCE Electric heating. Primary heating input energy is accumulated to end use HTG of meter rsElecMtr.
ACPKGROOMFURNACE Packaged room cooling and (separate) furnace heating.
ACPKGROOMRESISTANCE Packaged room cooling and electric resistance heating.
COMBINEDHEATDHW Combined heating / DHW. Use rsCHDHWSYS to specify the DHWSYS that provides hot water to the coil in this RSYS. No cooling.
ACCOMBINEDHEATDHW Compressor-based cooling; COMBINEDHEATDHW heating.
ACPMCOMBINEDHEATDHW Compressor-based cooling modeled per PERFORMANCEMAP specified in rsPerfMapClg; COMBINEDHEATDHW heating.
FANCOIL Coil-based heating and cooling. No primary (fuel-using) equipment is modeled. rsLoadMtr, rsHtgLoadMtr, and rsClgLoadMtr are typically used to record loads for linking to an external model.
Units Legal Range Default Required Variability
one of above choices ACFURNACE No constant

rsDesc

Type: string

Text description of system, included as documentation in debugging reports such as those triggered by rsGeneratePerfMap=YES

Units Legal Range Default Required Variability
string none No constant

rsModeCtrl

Type: choice

Specifies systems heating/cooling availability during simulation.

OFF System is off (neither heating nor cooling is available)
HEAT System can heat (assuming rsType can heat)
COOL System can cool (assuming rsType can cool)
AUTO System can either heat or cool (assuming rsType compatibility). First request by any zone served by this RSYS determines mode for the current time step.
Units Legal Range Default Required Variability
OFF, HEAT, COOL, AUTO AUTO No hourly

rsGeneratePerfMap

Type: choice

Generate performance map(s) for this RSYS. Comma-separated text is written to file PM_[rsName].csv. This is a debugging capability that is not necessarily maintained. The format of the generated csv text file may change and is unrelated to the PERFORMANCEMAP input scheme used via rsPerfMapHtg and rsPerfMapClg.

Units Legal Range Default Required Variability
YES, NO NO No constant

rsFanTy

Type: choice

Specifies fan (blower) position relative to primary heating or cooling source (i.e. heat exchanger or heat pump coil for heating and AC coil for cooling). The blower position determines where fan heat is added to the RSYS air stream and thus influences the coil entering air temperature.

Units Legal Range Default Required Variability
BLOWTHRU, DRAWTHRU BLOWTHRU No constant

rsFanMotTy

Type: choice

Specifies type of motor driving the fan (blower). This is used in the derivation of the coil-only cooling capacity for the RSYS.

PSC Permanent split capacitor
BPM Brushless permanent magnet (aka ECM)
Units Legal Range Default Required Variability
PSC, BPM PSC No constant

rsAdjForFanHt

Type: choice

Fan heat adjustment with two options Yes or no. Yes: fanHtRtd derived from rsFanTy and removed from capacity and input values. No: no rated fan heat adjustments.

rsElecMtr

Type: mtrName

Name of METER object, if any, by which system’s electrical energy use is recorded (under appropriate end uses).

Units Legal Range Default Required Variability
name of a METER none No constant

rsFuelMtr =mtrName

Name of METER object, if any, by which system’s fuel energy use is recorded (under appropriate end uses).

Units Legal Range Default Required Variability
name of a METER none No constant

rsLoadMtr =ldMtrName\ rsHtgLoadMtr =ldMtrName\ rsClgLoadMtr =ldMtrName

Names of LOADMETER objects, if any, to which the system’s heating and/or cooling loads are recorded. Loads are the gross heating and cooling energy added to (or removed from) the air stream. Fan heat, auxiliary heat, and duct losses are not included in loads values.

rsLoadMtr accumulates both heating (> 0) and cooling (< 0) loads. rsHtgLoadMtr accumulates only heating loads. rsClgLoadMtr accumulates only cooling loads. This arrangement accomodates mixed heating and cooling source configurations. For example, loads can be tracked appropriately in a building that has multiple cooling sources and a single heating source.

rsLoadMtr should not specify the same LOADMETER as rsHtgLoadMtr or rsClgLoadMtr since this would result in double counting.

Units Legal Range Default Required Variability
name of a LOADMETER none No constant

rsSrcSideLoadMtr=ldMtrName\ rsHtgSrcSideLoadMtr =ldMtrName\ rsClgSrcSideLoadMtr =ldMtrName

Name of LOADMETER objects, if any, to which the system’s source-side heat transfers are recorded. For DX systems, this is the outdoor coil heat transfer. For other types, source-side values are the same as the indoor coil loads reported via rsLoadMtr.

rsSrcSideLoadMtr accumulates both heating (> 0) and cooling (< 0) transfers. rsHtgSrcSideLoadMtr accumulates only heating transfers. rsClgSrcSideLoadMtr accumulates only cooling transfers. This arrangement accomodates mixed heating and cooling source configurations.

rsSrcSideLoadMtr should not specify the same LOADMETER as rsHtgSrcSideLoadMtr or rsClgSrcSideLoadMtr since this would result in double counting.

Units Legal Range Default Required Variability
Name of a LOADMETER No constant

rsCHDHWSYS

Type: dhwsysName

DHWSYS hot water source for this RSYS, required when rsType is COMBINEDHEATDHW or ACCOMBINEDHEATDHW. The specified DHWSYS must include a DHWHEATER of whType=ASHPX or RESISTANCEX.

Units Legal Range Default Required Variability
Name of a DHWSYS none if combined heat/DHW constant

rsAFUE

Type: float

Heating Annual Fuel Utilization Efficiency (AFUE).

Units Legal Range Default Required Variability
0 \(<\) x \(\le\) 1 0.9 if furnace, 1.0 if resistance No constant

rsCapH

Type: float

Heating capacity, used when rsType is ACFURNACE, ACRESISTANCE, FURNACE, WSHP or RESISTANCE.

If rsType=WSHP, rsCapH is at source fluid temperature = 68 oF.

Units Legal Range Default Required Variability
Btu/hr AUTOSIZE or x \(\ge\) 0 0 No constant

rsTdDesH

Type: float

Nominal heating temperature rise (across system, not at zone) used during autosizing (when capacity is not yet known) and to derive heating air flow rate from heating capacity.

Units Legal Range Default Required Variability
oF x \(>\) 0 30 oF if heat pump else 50 oF No constant

rsFxCapH

Type: float

Heating autosizing capacity factor. If AUTOSIZEd, rsCapH or rsCap47 is set to rsFxCapH \(\times\) (peak design-day load). Peak design-day load is the heating capacity that holds zone temperature at the thermostat set point during the last substep of all hours of all design days.

Units Legal Range Default Required Variability
x \(>\) 0 1.4 No constant

rsFanPwrH

Type: float

Heating operating fan power. For most rsTypes, heating air flow is calculated from heating capacity and rsTdDesH. The default value of rsFanPwrH is .365 W/cfm except 0.273 W/cfm is used when rsType=COMBINEDHEATDHW and rsType=ACCOMBINEDHEATDHW.

Units Legal Range Default Required Variability
W/cfm x \(\ge\) 0 see above No constant

rsHSPF

Type: float

For rsType=ASHP, Heating Seasonal Performance Factor (HSPF).

Units Legal Range Default Required Variability
Btu/Wh x \(>\) 0 none Yes if rsType=ASHP constant

rsCap47

Type: float

For rsType=ASHP, rated heating capacity at outdoor dry-bulb temperature = 47 oF.

If rsType=ASHP and both rsCapC and rsCap47 are autosized, both are set to the larger consistent value using rsCapRat9547 (after application of rsFxCapH and rsFxCapC).

Units Legal Range Default Required Variability
Btu/Wh AUTOSIZE or x \(>\) 0 Calculated from rsCapC No constant

rsCap35

Type: float

For rsType=ASHP, rated heating capacity at outdoor dry-bulb temperature = 35 oF. rsCap35 typically reflects reduced capacity due to reverse (cooling) heat pump operation for defrost.

Units Legal Range Default Required Variability
Btu/Wh x \(>\) 0 Calculated from rsCap47 and rsCap17 No constant

rsCap17

Type: float

For rsType=ASHP, rated heating capacity at outdoor dry-bulb temperature = 17 oF.

Units Legal Range Default Required Variability
Btu/Wh x \(>\) 0 Calculated from rsCap47 No constant

rsCOP95

Type: float

For rsType=ASHP, rated heating coefficient of performance at outdoor dry-bulb temperature = 95 oF.

Units Legal Range Default Required Variability
x \(>\) 0 Calculated from rsCap95 No constant

rsCOP47

Type: float

For rsType=ASHP, rated heating coefficient of performance at outdoor dry-bulb temperature = 47 oF. For rsType=WSHP, rated heating coefficient of performance at source fluid temperature = 68 oF.

Units Legal Range Default Required Variability
x \(>\) 0 Estimated from rsHSPF, rsCap47, and rsCap17 No constant

rsCOP35

Type: float

For rsType=ASHP, rated heating coefficient of performance at outdoor dry-bulb temperature = 35 oF.

Units Legal Range Default Required Variability
x \(>\) 0 Calculated from rsCap35, rsCap47, rsCap17, rsCOP47, and rsCOP17 No constant

rsCOP17

Type: float

For rsType=ASHP, rated heating coefficient of performance at outdoor dry-bulb temperature = 17 oF.

Units Legal Range Default Required Variability
x \(>\) 0 Calculated from rsHSPF, rsCap47, and rsCap17 No constant

rsCapRat1747

Type: float

Ratio of rsCAP17 over rsCAP47.

Units Legal Range Default Required Variability
x \(>\) 0 Based on HSPF or
other correlations No Start of a run

rsCapRat9547

Type: float

Ratio of rsCAP95 to rsCAP47. This ratio is used for inter-defaulting rsCap47 and rsCapC such that they have consistent values as is required given that a heat pump is a single device. If not given, rsCapRat9547 is determined during calculations using the relationship cap95 = 0.98 * cap47 + 180 (derived via correlation of capacities of a set of real units).

Units Legal Range Default Required Variability
x \(>\) 0 See above No constant

rsCapRatCH

Type: float

For WSHP only: ratio of rsCapC to rsCapH. Used to derive capacity during autosizing or when only one capacity is specified.

Units Legal Range Default Required Variability
.3 \(\leq\) x \(<\) 2 0.8 No Start of a run

rsPerfMapHtg

Type: performanceMapName

Specifies the heating performance PERFORMANCEMAP for RSYSs having rsType=ASHPPM. The PERFORMANCEMAP must have grid variables outdoor drybulb and compressor speed (in that order) and lookup values of net capacity ratios and COP. See example in PERFORMANCEMAP.

Units Legal Range Default Required Variability
Name of a PERFORMANCEMAP if rsType specifies a performance map model Start of a run

rsPerfMapClg

Type: performanceMapName

Specifies the cooling performance PERFORMANCEMAP for RSYSs having rsType=ASHPPM, ACPM, ACPMFURNACE, ACPMRESISTANCE, or ACPMCOMBINEDHEATDHW. The PERFORMANCEMAP must have grid variables outdoor drybulb and compressor speed (in that order) and lookup values of net capacity ratios and COP. See example in PERFORMANCEMAP.

Units Legal Range Default Required Variability
Name of a PERFORMANCEMAP if rsType specifies a performance map model Start of a run

rsTypeAuxH

Type: choice

For rsType=ASHP, type of auxiliary heat. Auxiliary heating is used when heatpump capacity is insufficient to maintain zone temperature and during reverse-cycle defrost operation (if rsDefrostModel=REVCYCLEAUX). If rsTypeAuxH=Furnace, energy use for auxiliary heat is accumulated to end use HPBU of meter rsFuelMtr (if specified). If rsTypeAuxH=Resistance, energy use for auxiliary heat is accumulated to end use HPBU of meter rsElecMtr (if specified).

Choice Description
NONE No auxiliary heat
RESISTANCE Electric resistance (aka strip heat)
FURNACE Fuel-fired
Units Legal Range Default Required Variability
See table above RESISTANCE No constant

rsCtrlAuxH

Type: choice

For rsType=ASHP, type of auxiliary heating control.

Choice Description
LOCKOUT Compressor locked out if any auxiliary heating control
CYCLE Compressor runs continuously and auxiliary cycles
ALTERNATE Alternates between compressor and auxiliary
Units Legal Range Default Required Variability
See table above ALTERNATE if rsTypeAuxH=FURNACE else CYCLE No Start of a run

rsCapAuxH

Type: float

For rsType=ASHP, auxiliary heating capacity. If AUTOSIZEd, rsCapAuxH is set to the peak heating load evaluated at the heating design temperature (Top.heatDsTDbO).

Units Legal Range Default Required Variability
Btu/hr AUTOSIZE or x \(\ge\) 0 0 No constant

rsAFUEAuxH

Type: float

For rsType=ASHP, auxiliary heat annualized fuel utilization efficiency.

Units Legal Range Default Required Variability
x \(>\) 0 0.9 if rsTypeAuxH=FURNACE else 1 No constant

rsDefrostModel

Type: choice

Selects modeling options for ASHP outdoor coil defrosting when 17 oF < TDbO < 45 oF. In this temperature range, heating capacity and/or efficiency are typically reduced due to frost accumulation on the outdoor coil.

NONE Defrost is not modeled. When 17 oF < TDbO < 45 oF, capacity and efficiency are determined by interpolation using unmodified 17 oF and 47 oF data.
REVCYCLE Reverse compressor (cooling) operation. Net capacity and efficiency is derived from rsCap17/rsCOP17 and rsCap35/rsCOP35 using linear interpolation. Auxiliary heat is not modeled.
REVCYCLEAUX Reverse compressor (cooling) operation with provision of sufficient auxiliary heat to make up the loss of heating capacity. Auxiliary heating is typically used to prevent cold air delivery to zones during the defrost cycle.
Units Legal Range Default Required Variability
one of above choices REVCYCLEAUX No constant

rsSHRtarget

Type: float

Nominal target for sensible heat ratio (for fancoil).

Units Legal Range Default Required Variability
x \(>\) 0 0.7 No subhour

rsFxCapAuxH

Type: float

Auxiliary heating autosizing capacity factor. If AUTOSIZEd, rsCapAuxH is set to rsFxCapAuxH \(\times\) (peak design-day load). Peak design-day load is the heating capacity that holds zone temperature at the thermostat set point during the last substep of all hours of all design days.

Units Legal Range Default Required Variability
x \(>\) 0 1 No constant

rsSEER

Type: float

Cooling rated Seasonal Energy Efficiency Ratio (SEER).

Units Legal Range Default Required Variability
Btu/Wh x \(>\) 0 none Yes constant

rsEER

Type: float

Cooling Energy Efficiency Ratio (EER) at standard AHRI rating conditions (outdoor drybulb of 95 oF and entering air at 80 oF drybulb and 67 oF wetbulb). For rsType=WSHP, rated EER at fluid source temperature = 86 oF.

Units Legal Range Default Required Variability
Btu/Wh x \(>\) 0 Estimated from SEER unless WSHP Yes for WSHP else No constant

rsCapC

Type: float

Net cooling capacity at standard rating conditions (outdoor drybulb temperature = 95 oF for air source or fluid source temperature = 86 oF for water source).

If rsType=ASHP and both rsCapC and rsCap47 are autosized, both are set to the larger consistent value using rsCapRat9547 (after application of rsFxCapH and rsFxCapC).

If rsType=WSHP and both rsCapC and rsCapH are autosized, both are set to the larger consistent value using rsCapRatCH (after application of rsFxCapH and rsFxCapC).

Units Legal Range Default Required Variability
Btu/hr AUTOSIZE or x \(\le\) 0 (x \(>\) 0 coverted to \(<\) 0) none Yes if rsType includes cooling constant

rsTdDesC

Type: float

Nominal cooling temperature fall (across system, not zone) used during autosizing (when capacity is not yet known).

Units Legal Range Default Required Variability
oF x \(<\) 0 -25 No constant

rsFxCapC

Type: float

Cooling autosizing capacity factor. rsCapC is set to rsFxCapC \(\times\) (peak design-day load). Peak design-day load is the cooling capacity that holds zone temperature at the thermostat set point during the last substep of all hours of all design days.

Units Legal Range Default Required Variability
x \(>\) 0 1.4 No constant

rsFChg

Type: float

Cooling compressor capacity factor. The gross cooling capacity is adjusted by the factor rsFChg as specified by California Title 24 procedures.

Units Legal Range Default Required Variability
x \(>\) 0 1 (no effect) No constant

rsVFPerTon

Type: float

Standard air volumetric flow rate per nominal ton of cooling capacity.

Units Legal Range Default Required Variability
cfm/ton 150 \(\le\) x \(\le\) 500 350 No constant

rsFanPwrC

Type: float

Cooling fan power.

Units Legal Range Default Required Variability
W/cfm x \(\ge\) 0 0.365 No constant

rsASHPLockOutT

Type: float

Source air dry-bulb temperature below which the air source heat pump compressor does not operate.

Units Legal Range Default Required Variability
oF (no lockout) No hourly

rsCdH

Type: float

Heating cyclic degradation coefficient, valid only for compressor-based heating (heat pumps).

Units Legal Range Default Required Variability
0 \(\le\) x \(\le\) 0.5 ASHPHYDRONIC: 0.25 ASHP: derived from rsHSPF No hourly

rsCdC

Type: float

Cooling cyclic degradation coefficient, valid for configurations having compressor-based cooling.

Units Legal Range Default Required Variability
0 \(\le\) x \(\le\) 0.5 0 No hourly

rsFEffH

Type: float

Heating efficiency factor. At each time step, the heating efficiency is multiplied by rsFEffH.

Units Legal Range Default Required Variability
x \(>\) 0 1 No subhourly

rsFEffAuxHBackup

Type: float

Backup auxiliary heating efficiency factor. At each time step, the backup heating efficiency is multiplied by rsFEffAuxHBackup. Backup auxiliary heating is typically provided by electric resistance "strip heat" but may be provided by a furnace (see rsTypeAuxH). If rsTypeAuxH is not "none", backup heat operates when air source heat pump compressor capacity is insufficient to meet heating load. See also rsFEffAuxHDefrost.

Units Legal Range Default Required Variability
x \(>\) 0 1 No subhourly

rsFEffAuxHDefrost

Type: float

Defrost auxiliary heating efficiency factor. At each time step, the defrost auxiliary heating efficiency is multiplied by rsFEffAuxHDefrost. Defrost auxiliary heating is typically provided by electric resistance "strip heat" but may be provided by a furnace (see rsTypeAuxH). If rsDefrostModel=REVCYCLEAUX, defrost auxiliary heat operates during air source heat pump defrost mode. Since defrost and backup heating are generally provided by the same equipment, rsFEffAuxHDefrost and rsFEffAuxHBackup are usually set to the same value, but separate inputs are available for special cases.

Units Legal Range Default Required Variability
x \(>\) 0 1 No subhourly

rsFEffC

Type: float

Cooling efficiency factor. At each time step, the cooling efficiency is multiplied by rsEffC.

Units Legal Range Default Required Variability
x \(>\) 0 1 No subhourly

rsCapNomH

Type: float

Heating nominal capacity. Provides type-independent probe source for RSYS heating capacity. Daily variability is specified to support value changes during AUTOSIZEing. Values set via input are typically constant.

Units Legal Range Default Required Variability
Btu/hr x \(\ge\) 0 no heating: 0 heat pump: rsCap47 (input or AUTOSIZEd) other: rsCapH (input or AUTOSIZEd) No daily

rsCapNomC

Type: float

Cooling nominal capacity. Provides type-independent probe source for RSYS cooling capacity. Daily variability is specified to support value changes during AUTOSIZEing. Values set via input are typically constant.

Units Legal Range Default Required Variability
Btu/hr x \(\ge\) 0 no cooling: 0 other: rsCap95 (input or AUTOSIZEd) No daily

rsDSEH

Type: float

Heating distribution system efficiency. If given, (1-rsDSEH) of RSYS heating output is discarded. Cannot be combined with more detailed DUCTSEG model.

Units Legal Range Default Required Variability
0 < x < 1 (use DUCTSEG model) No hourly

rsDSEC

Type: float

Cooling distribution system efficiency. If given, (1-rsDSEC) of RSYS cooling output is discarded. Cannot be combined with more detailed DUCTSEG model.

Units Legal Range Default Required Variability
0 < x < 1 (use DUCTSEG model) No hourly

rsOAVType=choice

Type of central fan integrated (CFI) outside air ventilation (OAV) included in this RSYS. OAV systems use the central system fan to circulate outdoor air (e.g. for night ventilation).

OAV cannot operate simultaneously with whole building ventilation (operable windows, whole house fans, etc.). Availability of ventilation modes is controlled on an hourly basis via Top ventAvail.

NONE No CFI ventilation capabilities
FIXED Fixed-flow CFI (aka SmartVent). The specified rsOAVVfDs is used whenever the RSYS operates in OAV mode.
VARIABLE Variable-flow CFI (aka NightBreeze). Flow rate is determined at midnight based on prior day's average dry-bulb temperature according to a control algorithm defined by the NightBreeze vendor.
Units Legal Range Default Required Variability
NONE, FIXED, VARIABLE none No constant

rsOAVVfDs=float

Design air volume flow rate when RSYS is operating in OAV mode.

Units Legal Range Default Required Variability
cfm x \(\ge\) 0 none if rsOAVType $
e$ NONE constant

rsOAVVfMinF=float

Minimum air volume flow rate fraction when RSYS is operating in OAV mode. When rsOAVType=VARIABLE, air flow rate is constrained to rsOAVVfMinF * rsOAVVfDs or greater.

Units Legal Range Default Required Variability
0 \(\le\) x \(\le\) 1 0.2 No constant

rsOAVFanPwr=float

RSYS OAV-mode fan power.

Units Legal Range Default Required Variability
W/cfm 0 < x \(\le\) 5 per rsOAVTYPE FIXED: rsFanPwrC VARIABLE: NightBreeze vendor curve based on rsOAVvfDs No constant

rsOAVTDbInlet

Type: float

OAV inlet (source) air temperature. Supply air temperature at the zone is generally higher due to fan heat. Duct losses, if any, also alter the supply air temperature.

Units Legal Range Default Required Variability
oF x \(\ge\) 0 Dry-bulb temperature from weather file No hourly

rsOAVTdiff

Type: float

OAV temperature differential. When operating in OAV mode, the zone set point temperature is max( znTD, inletT+rsOAVTdiff). Small values can result in inadvertent zone heating, due to fan heat.

Units Legal Range Default Required Variability
oF x \(>\) 0 5 oF No hourly

rsOAVReliefZn

Type: znName

Name of zone to which relief air is directed during RSYS OAV operation, typically an attic zone. Relief air flow is included in the target zone's pressure and thermal balance.

Units Legal Range Default Required Variability
name of ZONE none if rsOAVType $
e$ NONE constant

rsParElec

Type: float

Parasitic electrical power. rsParElec is unconditionally accumulated to end use AUX of rsElecMtr (if specified) and has no other effect.

Units Legal Range Default Required Variability
W 0 No hourly

rsParFuel

Type: float

Parasitic fuel use. rsParFuel is unconditionally accumulated to end use AUX of sFuelMtr (if specified) and has no other effect.

Units Legal Range Default Required Variability
Btuh 0 No hourly

rsRhIn

Type: float

Entering air relative humidity (for model testing).

Units Legal Range Default Required Variability
W/cfm 0 \(\le\) x \(\le\) 1 Derived from entering air state No constant

rsTdbOut

Type: float

Air dry-bulb temperature at the outdoor portion of this system.

Units Legal Range Default Required Variability
oF x \(\ge\) 0 From weather file No hourly

endRSYS

Optionally indicates the end of the RSYS definition.

Units Legal Range Default Required Variability
none No constant