Skip to content

DHWLOOPBRANCH

DHWLOOPBRANCH constructs one or more objects representing a branch pipe from the preceding DHWLOOPSEG. A DHWLOOPSEG can have any number of DHWLOOPBRANCHs to represent pipe runs with differing sizes, insulation, or surrounding conditions.

wbName

Optional name of segment; give after the word “DHWLOOPBRANCH” if desired.

Units Legal Range Default Required Variability
63 characters none No constant

wbMult

Type: float

Specifies the number of identical DHWLOOPBRANCHs. Note may be non-integer.

Units Legal Range Default Required Variability
x \(>\) 0 1 No constant

wbLength

Type: float

Length of branch.

Units Legal Range Default Required Variability
ft x \(\ge\) 0 0 No constant

wbSize

Type: float

Nominal size of pipe. CSE assumes the pipe outside diameter = size + 0.125 in.

Units Legal Range Default Required Variability
in x \(>\) 0 none Yes constant

wbInsulK

Type: float

Pipe insulation conductivity

Units Legal Range Default Required Variability
Btuh-ft/ft2-oF x \(>\) 0 0.02167 No constant

wbInsulThk

Type: float

Pipe insulation thickness

Units Legal Range Default Required Variability
in x \(\ge\) 0 1 No constant

wbExH

Type: float

Combined radiant/convective exterior surface conductance between insulation (or pipe if no insulation) and surround.

Units Legal Range Default Required Variability
Btuh/ft2-oF x \(>\) 0 1.5 No hourly

wbExCnd

Type: choice

Specify exterior conditions.

Choice Description
ADIABATIC Adiabatic on other side
AMBIENT Ambient exterior
SPECT Specify temperature
ADJZN Adjacent zone
GROUND Ground conditions
Units Legal Range Default Required Variability
See table above SPECT No constant

wbAdjZn

Type: float

Boundary conditions for adjacent zones.

Units Legal Range Default Required Variability
x \(>\) 0 0.0 No runly

wbExTX

Type: float

External boundary conditions.

Units Legal Range Default Required Variability
x \(>\) 0 70.0 No runly

wbFUA

Type: float

Adjustment factor applied to branch UA. UA is derived (from wbSize, wbLength, wbInsulK, wbInsulThk, and wbExH) and then multiplied by wbFUA. Used to represent e.g. imperfect insulation. Note that parent DHWLOOP wlFUA does not apply to DHWLOOPBRANCH (only DHWLOOPSEG)

Units Legal Range Default Required Variability
x \(\ge\) 0 1 No constant

wbExT

Type: float

Surrounding equivalent temperature.

Units Legal Range Default Required Variability
oF x \(>\) 0 70 No hourly

wbFlow

Type: float

Branch flow rate assumed during draw.

Units Legal Range Default Required Variability
gpm x \(\ge\) 0 2 No hourly

wbFWaste

Type: float

Number of times during the hour when the branch volume is discarded.

Units Legal Range Default Required Variability
x \(\ge\) 0 0 No hourly

endDHWLOOPBRANCH

Optionally indicates the end of the DHWLOOPBRANCH definition.

Units Legal Range Default Required Variability
none none No

Related Probes: