CSE User's Manual

California Simulation Engine

6.68 zhx (owner: zone)

@zhx[1..].

NameInput?Runtime?TypeVariabilityDescription
nameXstringconstant
zhxTyXunrecognizedrun start time (of each phase, autoSize or simulate)Zhx type (cndtypes.def): lhso, lhsth, arso, arsth, arstc, or (future) nv.
spXnumberhourlySetpoint if heat xfer is tstat controlled (settmp), else unused (hourly variability)
spPriXinteger numberrun start time (of each phase, autoSize or simulate)Setpoint priority: low #’s used first if setpoints equal, so can eg peg air heat b4 using local heat.
uiXinteger numberrun start time (of each phase, autoSize or simulate)Terminal tu subscript if a term cap type
ziXinteger numberrun start time (of each phase, autoSize or simulate)Zone znr subscript always – for term cap or vent zhx. when stable, just use ownti?
aiXinteger numberrun start time (of each phase, autoSize or simulate)0 or ah ss (subscript) of air handler supplying ar zhx (copied from tu).
xiLhXinteger numberrun start time (of each phase, autoSize or simulate)Subscr of local heat zhx for same terminal if any, else 0; not set for self.
xiArHXinteger numberrun start time (of each phase, autoSize or simulate)Was xiheat. subscr of air heat or air set output zhx for same terminal, if any, else 0
xiArCXinteger numberrun start time (of each phase, autoSize or simulate)Xicool. subscr of air cool zhx for same terminal, if any, else 0
nxZhx4zXinteger numberrun start time (of each phase, autoSize or simulate)Chain: 0 or subscript of next terminal zhx for this zone; 0?? if vent; head znr.zhx1.
nxZhxSt4zXinteger numberhourlyChain: 0 or ss of next settmp zhx for this zone; head znr.zhx1st; kept sorted on sp/pri at runtime.
nxZhx4aXinteger numberrun start time (of each phase, autoSize or simulate)Chain: 0 or subscript of next terminal zhx for this air handler; head ah.zhx1.
mdaXinteger numberhourlyFor settmp, mode (mdseq[] subscr) in which this is active (ctrl’d by its sp) zhx.