6.65 towerPlant

@towerPlant[1..].

NameInput?Runtime?TypeVariabilityDescription
nameXXstringconstant
ctNXXinteger numberautosize and simulate phase start timeNumber of towers. niles’ ctno. default 1.
tpStgXXunrecognizedautosize and simulate phase start timeStaging choice, default together. niles’ stgop.
tpTsSpXXnumberhourlyTowers delivered water setpoint temperature (niles’ twosp). degrees f, hourly, default 85f.
tpMtrXXinteger numberinput timeSubscript of meter object to which tower fan energy input will be posted,
ctTyXXunrecognizedautosize and simulate phase start timeCooling tower fan control type choice: onespeed (default), twospeed, or variable.
ctLoSpdXXnumberautosize and simulate phase start timeLow speed for a twospeed fan, as a fraction of full cfm. default 0.5.
ctShaftPwrXXnumberautosize and simulate phase start timeShaft power of one tower fan motor. rqd. user name ‘shaftbhp’.
ctMotEffXXnumberautosize and simulate phase start timeMotor (and drive, if any) efficiency, default 0.88
ctFcOne.k[0]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcOne.k[1]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcOne.k[2]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcLo.k[0]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcLo.k[1]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcLo.k[2]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcHi.k[0]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcHi.k[1]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcHi.k[2]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcVar.k[0]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcVar.k[1]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcVar.k[2]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcVar.k[3]XXnumberrun start time (of each phase, autoSize or simulate)
ctFcVar.k[4]XXnumberrun start time (of each phase, autoSize or simulate)
ctCapDsXXnumberrun start time (of each phase, autoSize or simulate)Design capacity, btuh. (replaces niles’ design water inlet temperature.)
ctVfDsXXnumberautosize and simulate phase start timeDesign air flow volume rate through tower / full speed fan flow??, cfm, rqd.
ctGpmDsXXnumberrun start time (of each phase, autoSize or simulate)Design water flow rate, gpm. default: sum of connected heat rejection pump capacities / ctn.
ctTDbODsXXnumberautosize and simulate phase start timeDesign outdoor drybulb temperature, f, rqd. (only needed to convert ctvfds from cfm to lb/hr).
ctTWbODsXXnumberautosize and simulate phase start timeDesign outdoor wetbulb temperature, f, rqd.
ctTwoDsXXnumberautosize and simulate phase start timeDesign leaving water temperature, f, default 85.
ctCapOdXXnumberrun start time (of each phase, autoSize or simulate)Off-design capacity, btuh. (replaces niles’ design water inlet temperature.)
ctVfOdXXnumberautosize and simulate phase start timeOff-design air flow volume rate through one tower, cfm, must != ctvfds.
ctGpmOdXXnumberrun start time (of each phase, autoSize or simulate)Off-design water flow rate, gpm. default: sum of connected heat rejection pump capacities/ ctn.
ctTDbOOdXXnumberautosize and simulate phase start timeOff-design outdoor drybulb temperature, f. (only needed to convert ctvfod from cfm to lb/hr).
ctTWbOOdXXnumberautosize and simulate phase start timeOff-design outdoor wetbulb temperature, f.
ctTwoOdXXnumberautosize and simulate phase start timeOff-design leaving water temperature, f, default 85.
ctKXXnumberrun start time (of each phase, autoSize or simulate)Exponent in formula ntua = const * (mw/ma)^ctk, as alternative to “off design” inputs.
ctStkFlFrXXnumberautosize and simulate phase start timeStack effect flow: air flow that occurs thru tower when fan is off, as a fraction of ctvfds.
ctBldnXXnumberautosize and simulate phase start timeBlowdown rate: frac inflowing water bled down drain, to reduce impurities buildup. default .01.
ctDrftXXnumberautosize and simulate phase start timeDrift rate: frac inflowing water blown out of tower as droplets, w/o evaporating. default 0.
ctTWmXXnumberautosize and simulate phase start timeTemperature of water in mains, for makeup water. default 60.
cp1XXinteger numberrun start time (of each phase, autoSize or simulate)Subscript of 1st coolplant served by this towerplant. next is coolplant.nxcp4tp.
hl1XXinteger numberrun start time (of each phase, autoSize or simulate)Subscript of 1st hploop with hx served by this towerplant. next is hploop.nxhl4tp.
oneFanPXXnumberrun start time (of each phase, autoSize or simulate)
maDsXXnumberrun start time (of each phase, autoSize or simulate)
maOdXXnumberrun start time (of each phase, autoSize or simulate)
mwDsXXnumberrun start time (of each phase, autoSize or simulate)
mwOdXXnumberrun start time (of each phase, autoSize or simulate)
maOverMwDsXXnumberrun start time (of each phase, autoSize or simulate)Mads/mwds, precomputed in setup.
ntuADsXXnumberrun start time (of each phase, autoSize or simulate)Number of transfer units for air side at design conditions (niles ntuad)
ntuAOdXXnumberrun start time (of each phase, autoSize or simulate).. at off-design conditions, if given. member only as debug aid.
tpTsXXnumberend of each subhour
tpClfXXinteger numberend of each subhourCall-flag: set nz if must call tpcompute so it can test tr, etc to see if computation needed.
tpPtfXXinteger numberend of each subhourCompute-flag: set if must call tpcompute and it should unconditionally recompute.
trNxXXnumberend of each subhour
mwAllNxXXnumberend of each subhour
qLoadNxXXnumberend of each subhour
trXXnumberend of each subhour
mwAllXXnumberend of each subhour
qLoadXXnumberend of each subhour
mwi1XXnumberend of each subhour
qNeedXXnumberend of each subhour
qMax1XXnumberend of each subhour
qMin1XXnumberend of each subhour
towldCaseXXunrecognizedend of each subhourTower load case, tpcompute to endsubhr: facilitates deferring fan power calc
qMaxGuessXXnumberend of each subhourFor internal values for towmodel initial guess at next call for various towmodel calls.
qMinGuessXXnumberend of each subhour..
qLoGuessXXnumberend of each subhour..
qVarGuessXXnumberend of each subhour.., used via varspeedf
qVarTemXXnumberend of each subhour
puteTsXXnumberend of each subhour
nCtOpXXinteger numberend of each subhourNumber of tower fans operating
fXXnumberend of each subhourFraction of full speed (fraction on for one speed fan), for lead tower only if lead.
fanPXXnumberend of each subhourPlant’s fan input pwr this subhour (btuh!)
qXXnumberend of each subhourPower imparted to water, for change detection/probes/reports 10-19-92
tpTsSpPrXXnumberend of each subhourFor tpestimate
tpTsEstPrXXnumberend of each subhourFor tpestimate
tpTsPrXXnumberend of each subhourLeaving water temp at last tpcompute, f (unused?)
tDbOShPrXXnumberend of each subhourOutdoor drybulb temp at last tpcompute, f
wOShPrXXnumberend of each subhourOutdoor humidity ratio at last tpcompute, f