6.65 towerPlant
@towerPlant[1..].
Name | Input? | Runtime? | Type | Variability | Description |
---|---|---|---|---|---|
name | X | X | string | constant | – |
ctN | X | X | integer number | autosize and simulate phase start time | Number of towers. niles’ ctno. default 1. |
tpStg | X | X | unrecognized | autosize and simulate phase start time | Staging choice, default together. niles’ stgop. |
tpTsSp | X | X | number | hourly | Towers delivered water setpoint temperature (niles’ twosp). degrees f, hourly, default 85f. |
tpMtr | X | X | integer number | input time | Subscript of meter object to which tower fan energy input will be posted, |
ctTy | X | X | unrecognized | autosize and simulate phase start time | Cooling tower fan control type choice: onespeed (default), twospeed, or variable. |
ctLoSpd | X | X | number | autosize and simulate phase start time | Low speed for a twospeed fan, as a fraction of full cfm. default 0.5. |
ctShaftPwr | X | X | number | autosize and simulate phase start time | Shaft power of one tower fan motor. rqd. user name ‘shaftbhp’. |
ctMotEff | X | X | number | autosize and simulate phase start time | Motor (and drive, if any) efficiency, default 0.88 |
ctFcOne.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcOne.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcOne.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcLo.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcLo.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcLo.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcHi.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcHi.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcHi.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcVar.k[0] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcVar.k[1] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcVar.k[2] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcVar.k[3] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctFcVar.k[4] | X | X | number | run start time (of each phase, autoSize or simulate) | – |
ctCapDs | X | X | number | run start time (of each phase, autoSize or simulate) | Design capacity, btuh. (replaces niles’ design water inlet temperature.) |
ctVfDs | X | X | number | autosize and simulate phase start time | Design air flow volume rate through tower / full speed fan flow??, cfm, rqd. |
ctGpmDs | X | X | number | run start time (of each phase, autoSize or simulate) | Design water flow rate, gpm. default: sum of connected heat rejection pump capacities / ctn. |
ctTDbODs | X | X | number | autosize and simulate phase start time | Design outdoor drybulb temperature, f, rqd. (only needed to convert ctvfds from cfm to lb/hr). |
ctTWbODs | X | X | number | autosize and simulate phase start time | Design outdoor wetbulb temperature, f, rqd. |
ctTwoDs | X | X | number | autosize and simulate phase start time | Design leaving water temperature, f, default 85. |
ctCapOd | X | X | number | run start time (of each phase, autoSize or simulate) | Off-design capacity, btuh. (replaces niles’ design water inlet temperature.) |
ctVfOd | X | X | number | autosize and simulate phase start time | Off-design air flow volume rate through one tower, cfm, must != ctvfds. |
ctGpmOd | X | X | number | run start time (of each phase, autoSize or simulate) | Off-design water flow rate, gpm. default: sum of connected heat rejection pump capacities/ ctn. |
ctTDbOOd | X | X | number | autosize and simulate phase start time | Off-design outdoor drybulb temperature, f. (only needed to convert ctvfod from cfm to lb/hr). |
ctTWbOOd | X | X | number | autosize and simulate phase start time | Off-design outdoor wetbulb temperature, f. |
ctTwoOd | X | X | number | autosize and simulate phase start time | Off-design leaving water temperature, f, default 85. |
ctK | X | X | number | run start time (of each phase, autoSize or simulate) | Exponent in formula ntua = const * (mw/ma)^ctk, as alternative to “off design” inputs. |
ctStkFlFr | X | X | number | autosize and simulate phase start time | Stack effect flow: air flow that occurs thru tower when fan is off, as a fraction of ctvfds. |
ctBldn | X | X | number | autosize and simulate phase start time | Blowdown rate: frac inflowing water bled down drain, to reduce impurities buildup. default .01. |
ctDrft | X | X | number | autosize and simulate phase start time | Drift rate: frac inflowing water blown out of tower as droplets, w/o evaporating. default 0. |
ctTWm | X | X | number | autosize and simulate phase start time | Temperature of water in mains, for makeup water. default 60. |
cp1 | X | X | integer number | run start time (of each phase, autoSize or simulate) | Subscript of 1st coolplant served by this towerplant. next is coolplant.nxcp4tp. |
hl1 | X | X | integer number | run start time (of each phase, autoSize or simulate) | Subscript of 1st hploop with hx served by this towerplant. next is hploop.nxhl4tp. |
oneFanP | X | X | number | run start time (of each phase, autoSize or simulate) | – |
maDs | X | X | number | run start time (of each phase, autoSize or simulate) | – |
maOd | X | X | number | run start time (of each phase, autoSize or simulate) | – |
mwDs | X | X | number | run start time (of each phase, autoSize or simulate) | – |
mwOd | X | X | number | run start time (of each phase, autoSize or simulate) | – |
maOverMwDs | X | X | number | run start time (of each phase, autoSize or simulate) | Mads/mwds, precomputed in setup. |
ntuADs | X | X | number | run start time (of each phase, autoSize or simulate) | Number of transfer units for air side at design conditions (niles ntuad) |
ntuAOd | X | X | number | run start time (of each phase, autoSize or simulate) | .. at off-design conditions, if given. member only as debug aid. |
tpTs | X | X | number | end of each subhour | – |
tpClf | X | X | integer number | end of each subhour | Call-flag: set nz if must call tpcompute so it can test tr, etc to see if computation needed. |
tpPtf | X | X | integer number | end of each subhour | Compute-flag: set if must call tpcompute and it should unconditionally recompute. |
trNx | X | X | number | end of each subhour | – |
mwAllNx | X | X | number | end of each subhour | – |
qLoadNx | X | X | number | end of each subhour | – |
tr | X | X | number | end of each subhour | – |
mwAll | X | X | number | end of each subhour | – |
qLoad | X | X | number | end of each subhour | – |
mwi1 | X | X | number | end of each subhour | – |
qNeed | X | X | number | end of each subhour | – |
qMax1 | X | X | number | end of each subhour | – |
qMin1 | X | X | number | end of each subhour | – |
towldCase | X | X | unrecognized | end of each subhour | Tower load case, tpcompute to endsubhr: facilitates deferring fan power calc |
qMaxGuess | X | X | number | end of each subhour | For internal values for towmodel initial guess at next call for various towmodel calls. |
qMinGuess | X | X | number | end of each subhour | .. |
qLoGuess | X | X | number | end of each subhour | .. |
qVarGuess | X | X | number | end of each subhour | .., used via varspeedf |
qVarTem | X | X | number | end of each subhour | – |
puteTs | X | X | number | end of each subhour | – |
nCtOp | X | X | integer number | end of each subhour | Number of tower fans operating |
f | X | X | number | end of each subhour | Fraction of full speed (fraction on for one speed fan), for lead tower only if lead. |
fanP | X | X | number | end of each subhour | Plant’s fan input pwr this subhour (btuh!) |
q | X | X | number | end of each subhour | Power imparted to water, for change detection/probes/reports 10-19-92 |
tpTsSpPr | X | X | number | end of each subhour | For tpestimate |
tpTsEstPr | X | X | number | end of each subhour | For tpestimate |
tpTsPr | X | X | number | end of each subhour | Leaving water temp at last tpcompute, f (unused?) |
tDbOShPr | X | X | number | end of each subhour | Outdoor drybulb temp at last tpcompute, f |
wOShPr | X | X | number | end of each subhour | Outdoor humidity ratio at last tpcompute, f |